Shanghai Shanjie Electric S&T Co.,Ltd
Shanghai Shanjie Electric S&T Co.,Ltd
Chinese version

Variable-frequency power supply installation instructions

 

1. Please refer to the following specifications before installation.
Input: 220V Single Phase Power Source

Model

Input

Output

DD

Max. Current

Protection Switch

Wire Diameter

Max. Current

Wire Diameter

500VA

2.5A

3.5A

0.5mm^2

110V:4.2A
220V:2.1A

1.00mm^2
0.50mm^2

1KVA

5A

6.5A

1.0mm^2

110V:8.4A
220V:4.2A

2.00mm^2
1.00mm^2

 2KVA

10A

13A

2.0mm^2

110V:16.8A
220V:8.4A

3.50mm^2
2.00mm^2

 3KVA

15A

20A

3.0mm^2

110V:25.0A
220V:12.5A

5.00mm^2
2.50mm^2

 5KVA

25A

33A

5.0mm^2

110V:42.0A
220V:21.0A

8.00mm^2
4.00mm^2

10KVA

50A

65A

10.0mm^2

110V:84.0A
220V:42.0A

16.00mm^2
8.00mm^2

 

 

Input: 380V Single Phase Power Source

Model

Input

Output

SS

Max. Current

Protection Switch

SS

Max. Current

Protection Switch

  15KVA

25A

33A

5.0mm^2

110V:126.0A
220V:63.0A

25.00mm^2
13.00mm^2

20KVA

34A

44A

7.0mm^2

110V:168.0A
220V:84.0A

35.00mm^2
17.00mm^2

30KVA

50A

65A

10.0mm^2

110V:250.0A
220V:125.0A

50.00mm^2
25.00mm^2

45KVA

76A

100A

16.0mm^2

110V:378.0A
220V:189.0A

76.00mm^2
38.00mm^2

60KVA

100A

130A

30.0mm^2

110V:500.0A
220V:250.0A

100.00mm^2
50.00mm^2

100KVA

170A

220A

50.0mm^2

110V:750.0A
220V:375.0A

150.00mm^2
75.00mm^2

    • Determine the input voltage before using the power source.
    • Before connection to the power source, please make sure the G-N-L (single phase) specification is correct and the phase sequence for N-A-B-C (three phase) is configured correctly.
    • Before connection to the power source, turn all switches to OFF to make sure the device has no possible damage.
    • The power source can only be connected when the device specification exactly match that of the power source system.


地 址:上海市武宁路599弄3号206(上海电科所院内)  电 话: 86-21-51698706